Sr. No.
Name |
Specification |
Item Descriptions |
|
1. |
MotorTesting Panel |
Routine Testing Panel for Induction Motor 415V, 50A |
VIF Meter Setting For CT P : - Set 50A(Mains Supply) PT P : - Set 350V(Mains Supply) For PT S: - Set 350V(Mains Supply) |
2. |
Over Current Relay Settings |
DOL M1 Output 0.12KW-0.18KW |
For CT.P : - Set 10A | CT S : - Set 5A (Default) For SOC : - Set 0.8A | Trp : - Set 2 Sec |
3. |
Over Current Relay Settings |
DOL M2 Output 0.25KW-3KW |
For CT.P : - Set 10A | CT S : - Set 5A (Default) For SOC : - Set 7A | Trp : - Set 2 Sec |
Over Current Relay Settings |
DOL M3 Output 4KW-11KW |
For CT.P : - Set 30A | CT S : - Set 5A (Default) For SOC : - Set 20A | Trp : - Set 2 Sec |
|
Over Current Relay Settings |
15KW-22KW |
For CT.P : - Set 50A | CT S : - Set 5A (Default) For SOC : - Set 37A | Trp : - Set 2 Sec |
|
6. |
Power Analyzer |
Voltage: - 600 VAC Current: - 80 AAC Phase: - 3-Phase |
3-Phase Power Analyzer 600V (Phase Neutral) & 1050V (Phase to Phase) & 80A Direct Measurement with accuracy of 0.1% rdg + 0.1% rng |
7. |
Break Output |
5A |
415V 5A AC, 230V 5A AC, 110V 5A AC, 24V - 5A DC |